NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Context
Be careful when configuring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
12-21
Figure 12-21 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Figure 12-22 Setting alarm parameter 2
----End
Issue 08 (2021-09-17)
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
To set an alarm threshold, follow the instructions in this section.
The method for setting each alarm is the same. This section describes how to
set Threshold of Supply air high temperature alarm to 45.
If you need to change alarm settings, log in as the Admin user.
NO TICE
is displayed.
Copyright © Huawei Technologies Co., Ltd.
, as shown in
Figure
12-22.