Huawei NetCol5000-A050 User Manual page 145

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Menu
Settings >
Quick Settings
> T/H Sensor
Issue 08 (2021-09-17)
Parameter
Floor water
overflow
alarm action
In-cabinet
water
overflow
alarm action
Temperature
and humidity
control type
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Description
Set this parameter to
Shutdown, Inactivity,
Only indoor fan
running, or
Humidifier stopped
based on site
requirements.
Set this parameter to
Shutdown, Inactivity,
Only indoor fan
running, or
Humidifier stopped
based on site
requirements.
Cold aisle, Hot aisle,
Return air, and Supply
air can be set as
required. Enable the
corresponding sensors
based on the control
type.
Setting Guide
Retain the default
value.
Retain the default
value.
● When the
application
scenario is cold
or hot aisle
containment,
you are advised
to choose Cold
aisle if cold aisle
T/H sensors are
configured.
Choose Supply
air if no cold
aisle T/H sensors
are configured.
● When the
application
scenario is non-
aisle
containment,
you are advised
to choose
Return air.
Choose Cold
aisle if cold aisle
T/H sensors are
configured.
● You are not
advised to set
this parameter
as Hot aisle.
135