Step 2 Open the rear door and remove the air filter.
Step 3 Turn off the active power switch QF1 and standby power switch QF2. (For the
model with a single power supply, you do not need to turn off QF2.)
Step 4 Remove the pressure inlet tube.
Step 5 Remove the screws on the top cover of the differential pressure switch and cable
screws using a Phillips screwdriver and remove the cables.
Step 6 Remove the four screws using a Phillips screwdriver and remove the differential
pressure switch.
Step 7 Set the new differential pressure switch to 250 Pa.
Figure 11-8 Setting values for a differential pressure switch
Step 8 Install the new differential pressure switch and the pressure tube, and connect the
cables.