Figure 4-76 Bottom routing of the water inlet pipe
When routing pipes from the top, do not route the pipes over servers or other
devices to protect them from being affected by pipe leaks.
----End

4.8.9 Leakage Test with Nitrogen for Refrigerant Pipes

Prerequisites
● Refrigerant pipes have been welded.
● The needle valve plugs are tightened.
● The measuring range of a pressure gauge must be at least 4.0 MPa, and the
rubber hose must withstand a pressure of at least 4.5 MPa.
● Only nitrogen can be used for pressure preservation and leakage detection.
● During pressure preservation, do not remove the rubber hoses and pressure
gauges; otherwise, nitrogen may leak.
● When an air-cooled outdoor unit or a water cooling module is connected to the
outdoor side, perform the same operations on the refrigerant side for nitrogen
injection and pressure preservation.
Procedure
Step 1 Connect the rubber hoses, pressure gauges, reducing valve, and nitrogen cylinder
to the device. The pressure gauges and reducing valve are closed.
Issue 08 (2021-09-17)
NO TICE
NO TICE
If no low temperature component is installed on the outdoor side, connect
pipes as shown in
Figure
low-pressure and exhaust pipe needle valves simultaneously.
Copyright © Huawei Technologies Co., Ltd.
4-77, and charge nitrogen into the system from the
4 Installation