Huawei NetCol5000-A050 User Manual page 269

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 11-13 Removing the electric heating belt and compressor power cables
Step 7 Remove the compressor.
1.
Heat the suction angle valve thread connection position using a heat gun for
10 minutes. Secure the angle nut and pipe nut on the suction side, as shown
by (1) in
loosen the adjustable nut using a 36# adjustable wrench to separate the pipe
from the angle valve. After removing the valve, seal the suction vent
immediately.
Issue 08 (2021-09-17)
Figure
11-14, using two 30# adjustable wrenches respectively. Then
Copyright © Huawei Technologies Co., Ltd.
11 Parts Replacement