NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Issue 08 (2021-09-17)
CAN Teamwork
CAN
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
NO TE
● Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
● Customers can purchase an ECC and NetEco as the monitoring system.
Copyright © Huawei Technologies Co., Ltd.
4 Installation
RS485 Monitoring
Modbus-RTU
n seconds to
It takes 3 x
n units. If
collect data from
the time required for the host
to collect data from all units
does not meet the
performance requirements,
group the units.
● If units are not grouped (
= 1), set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for each unit.
● If units are grouped (
n ≤ 4), set
recommended:
RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the unit with the
COM/FE port connected.
Retain the default setting
(Disable) for other units.
n
n > 1;
113