How Do I Clear Component Runtime; How To Calibrate A Sensor - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 12-18 Delete historical alarms screen
Step 2 Tap Confirm to delete all historical alarms.
----End

12.13 How Do I Clear Component Runtime?

Context
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

12.14 How to Calibrate a Sensor

Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
Issue 08 (2021-09-17)
NO TE
After alarms are deleted, the operation is recorded in logs.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
12 FAQ
304

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents