Figure 4-29 Assembling an air deflector
Step 2 Install the assembled air deflector on the corridor module.
----End
4.6 (Optional) Installing T/H Sensors Outside a Cabinet
and Cables
Context
The T/H sensors outside the cabinet are used to detect the temperature and
humidity of remote points. The installation position can be determined based on
the site requirements. It is recommended that the T/H sensors be deployed near
heat sources, or near places that lack cooling capacity. Place the T/H sensors near
the cabinet. The sensors cannot face the air outlet of the device.
Procedure
Step 1 Connect the IN port on the first T/H sensor outside the cabinet to the RS485/12V
port on the main control module.
Step 2 Connect the OUT port on the T/H sensor outside the cabinet to the IN port on the
next T/H sensor outside the cabinet in series.