Huawei FusionCol8000-E240 User Manual page 112

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Settings > Quick
Settings > T/H Sensor
Issue 02 (2021-04-15)
Parameter
DO_1
DO_2
Floor water
overflow
alarm action
In-cabinet
water
overflow
alarm action
Temperature
and humidity
control type
Temperature
setpoint
Humidity
setpoint
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Guide
Set this parameter based on the
actual scenario.
NOTE
You are advised to retain the default
value.
Set this parameter based on the
actual scenario.
NOTE
You are advised to retain the default
value.
Set this parameter to Shutdown,
Inactivity, Only indoor fan running,
Humidifier stopped, or Comm &
Humid stopped based on site
requirements.
NOTE
You are advised to retain the default
value.
Set this parameter to Shutdown,
Inactivity, Only indoor fan running,
Humidifier stopped, or Comm &
Humid stopped based on site
requirements.
NOTE
You are advised to retain the default
value.
● When the application scenario is
non-aisle containment, you are
advised to choose Return air.
Choose Cold aisle if cold aisle T/H
sensors are configured.
● You are not advised to set this
parameter as Hot aisle.
After Temperature and humidity
control type and the temperature
value under this type are set, the
device operates based on the settings.
After Temperature and humidity
control type and the humidity value
under this type are set, the device
operates based on the settings.
103