Replacing A Liquid Level Sensor - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 5 Install the new fan drive and insert it into the corresponding slot in the power
distribution subrack.
Step 6 Flip the clip to lock the fan drive.
Figure 8-39 Installing the fan drive
Step 7 Install the adjustable side panel.
Step 8 Power on the smart cooling product, and choose Maint > Wizard Startup on the
home screen. Start the fan and check that the fan works properly and the smart
cooling product generates no alarms. Check that the smart cooling product works
properly before you exit.
----End

8.5.19 Replacing a Liquid Level Sensor

Prerequisites
Context
The liquid level sensor can be maintained only at the water tank.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the adjustable side panel.
Issue 02 (2021-04-15)
A liquid level sensor needs to be replaced.
A spare liquid level sensor of the same model is available and functional.
Tool: solid wrench
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
224