Replacing An Air Supply Fan - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the sealing plates.
Step 3 Remove the screws from the NTC temperature sensor fastener, and take out the
fastener.
Figure 8-17 Replacing an NTC temperature sensor
Step 4 Remove the screws that secure the NTC temperature sensor.
Step 5 Remove the interconnection terminal from the cable of the NTC temperature
sensor.
Step 6 Install the new NTC temperature sensor, reconnect the cables, and secure the NTC
temperature sensor in the original position.
Step 7 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End

8.5.12 Replacing an Air Supply Fan

Prerequisites
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Issue 02 (2021-04-15)
NO TICE
A fan needs to be replaced.
A spare fan of the same model is available and functional.
Tools: protection gloves, Phillips screwdriver, diagonal pliers, cable tie
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance