Alarm ID
Alarm Name
A282-10
Backup power phase
sequence abnormal
Auxiliary cooling
power phase sequence
abnormal
Auxiliary cooling
backup power phase
sequence abnormal
Issue 02 (2021-04-15)
Alarm
Severity
Major
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
● The power grid is
unstable.
● The phase C input
cable is faulty.
8 System Maintenance
Solution
1. Check the power
grid.
2. Rectify the fault of
the phase C input
cable.
171