8.5.2 Component Position (FDC Scenario)

Figure 8-2 Components to be replaced
(1) Differential
pressure switch
(5) Outdoor air intake
T/H sensor
(9) Compressor drive

8.5.3 Replacing an Air Filter (Building Scenario)

Prerequisites
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Replace the outdoor intake air filter (end). Remove the air filter fasteners and take
out the air filter from the end.
Issue 02 (2021-04-15)
(2) Indoor return air
T/H sensor
(6) Spray pump
(10) Liquid level sensor (11) Fan drive
An air filter needs to be replaced.
A spare air filter of the same model is available and functional.
When replacing an air filter, you need to use a maintenance platform. For
details how to prepare the platform, see
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
(3) Outdoor intake air
(4) Exhaust fan
filter
(7) Air supply fan
(8) Compressor
F Air filter Maintenance
Platform.