Huawei FusionCol8000-E240 User Manual page 169

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Alarm ID
Alarm Name
A092-01
Hot aisle low
temperature alarm
A093-01
High humidity alarm
Issue 02 (2021-04-15)
Alarm
Severity
Warning
Warning
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
● The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
● The thermal load
power is low.
● The ambient
temperature is
below the lower
threshold.
● The low
temperature alarm
threshold is
inappropriate.
● The value detected
by the temperature
sensor or
temperature and
humidity sensor is
different from the
actual value.
● The thermal load is
low.
● The ambient
humidity exceeds
the upper
threshold.
● The temperature
and humidity
sensor is not
installed in a
proper position.
● The high humidity
alarm threshold is
inappropriate.
● The value detected
by the temperature
and humidity
sensor is different
from the actual
value.
8 System Maintenance
Solution
1. Adjust the positions
of the temperature
sensors or
temperature and
humidity sensors.
2. Contact Huawei
technical support.
3. Measure the
ambient
temperature. Check
whether other
causes exist if the
alarm persists in a
long time after
startup.
4. Adjust the low
temperature alarm
threshold.
5. Calibrate or replace
the temperature
sensor or
temperature and
humidity sensor.
1. Contact Huawei
technical support.
2. Measure the
ambient humidity.
3. Adjust the position
of the temperature
and humidity
sensor.
4. Adjust the high
humidity alarm
threshold.
5. Calibrate or replace
the temperature
and humidity
sensor.
160