Huawei FusionCol8000-E240 User Manual page 248

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 9-6 Opening the side panel
Step 3 Insert the negative pressure tube of the differential pressure gauge into the unit
through the hole in the return air baffle plate of the fan for about 30 mm.
Step 4 Insert the positive pressure tube of the differential pressure gauge into the unit
through the cable hole for about 30 mm.
Figure 9-7 Pressure measurement points
(1) Pressure measurement point for the
negative pressure tube
Issue 02 (2021-04-15)
NO TE
The position of the side panel to be removed in the FDC scenario is the same as that in the
building scenario. This example shows how to open the side panel in the FDC scenario.
NO TE
The cross section of the pressure tubes must be perpendicular to the wind direction.
Copyright © Huawei Technologies Co., Ltd.
(2) Pressure measurement point for the
positive pressure tube
9 FAQ
239

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents