FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Locatio
Display Name
n
Outdoor intake air
3 temp/humid
Cold
Cold aisle 1 temp/
aisle
humid
Cold aisle 2 temp/
humid
Cold aisle 3 temp/
humid
Cold aisle 4 temp/
humid
Cold aisle 5 temp/
humid
Cold aisle 6 temp/
humid
Hot
Hot aisle 1 temp/
aisle
humid
Hot aisle 2 temp/
humid
Hot aisle 3 temp/
humid
Hot aisle 4 temp/
humid
Hot aisle 5 temp/
humid
Hot aisle 6 temp/
humid
● The default T/H sensor address is 1.
● Keep the last RS485_R DIP switch at OFF.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
Issue 02 (2021-04-15)
Addre
ss
32
11
12
13
14
15
16
21
22
23
24
25
26
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
DIP Switch No.
1
2
3
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
4
5
6
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
60