Removing Transport Fasteners And Desiccant Bags - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-16 Requirement for wrapping the electric heating belt
● The electric heating belt needs to be wrapped evenly on the drainpipe and
water refill pipe during onsite construction.
● Wrap the electric heating belt and then wrap the thermal insulation foam.
Ensure that the thermal insulation foam covers the temperature control switch
and temperature sensor probe. The thermal insulation foam must withstand a
temperature above 200°C.

4.3.6 Removing Transport Fasteners and Desiccant Bags

Procedure
Step 1 Remove the adjustable side panel of the compressor, and take out the desiccant
bag from the compressor.
Step 2 Open the electric control box and take out the desiccant bag from the box.
Step 3 Open the outdoor intake air filter and take out the desiccant bag from the
outdoor air intake compartment.
Step 4 Open the adjustable side panel and water barrier of the spray pump, and take out
the two desiccant bags from the spray pump compartment.
Step 5 Loosen the three transport fixing bolts of the compressor using a 13# solid wrench
and remove the sheet metal fasteners.
Issue 02 (2021-04-15)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 System Installation (FDC Scenario)
80

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents