Huawei FusionCol8000-E240 User Manual page 194

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Alarm ID
Alarm Name
A362-01
Spray pump 1 drive
power supply
abnormal
Spray pump 2 drive
power supply
abnormal
A363-01
Spray pump 1 drive
output abnormal
Spray pump 2 drive
output abnormal
A364-01
Spray pump 1 drive
overcurrent
Spray pump 2 drive
overcurrent
A371-01
Parts replacement
alarm
Issue 02 (2021-04-15)
Alarm
Severity
Major
Major
Major
Warning
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
● The power supply
to the spray pump
drive is abnormal.
● The cables to the
spray pump drive
are loose or
damaged.
● The output cables
to the spray pump
drive are loose or
damaged.
● The spray pump is
faulty.
● The spray pump
drive is faulty.
● The spray pump is
faulty.
● The spray pump
drive is faulty.
Reserved
8 System Maintenance
Solution
1. Check the power
supply to the spray
pump drive.
2. Check the cables to
the spray pump
drive.
1. Check the output
cables to the spray
pump drive.
2. Maintain or replace
the spray pump.
3. Maintain or replace
the spray pump
drive.
1. Maintain or replace
the spray pump.
2. Maintain or replace
the spray pump
drive.
Reserved
185

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents