Step 4 Set related parameters and tap Next until the home screen is displayed.
Table 6-2 Quick Settings parameters
Menu
Settings > Quick
Settings > Select
Language
Settings > Quick
Settings > Date & Time
Settings
Settings > Quick
Settings > Teamwork
Settings
Issue 02 (2021-04-15)
Parameter
Select
Language
Date format
Date settings
Time zone
Time
Teamwork
group No.
System
address
Teamwork
function
Networking
mode
Number of
systems in
this group
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Guide
Set the display language of the
display module based on the site
requirements.
Set the date display format of the
display module.
Set the date displayed on the display
module.
Set the time zone of the display
module.
Set the time displayed on the display
module.
Set the assigned teamwork group
number.
NOTE
The number of the teamwork group. This
parameter should be the same for all
units in the same teamwork group.
Set the planned unit address.
NOTE
The addresses of units in the same
teamwork group cannot be the same.
Enables or disables the teamwork
function. If the function is disabled,
the unit operates independently. If it
is enabled, the unit operates in a
team with other units.
NOTE
Set this parameter based on onsite heat
load distribution.
Set the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Enter the total number of smart
cooling products in the group.
100