FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 8-20 Removing the sheet metal that secures the fan
Step 5 Remove the protective cover from the fan terminal, cut off the cable tie that
secures the cable to the faulty fan, and remove the fan terminal.
Figure 8-21 Protective cover
(1) Protective cover
Step 6 Pull out the fan assembly.
● Two persons are required to pull out the fan.
● If only the first fan needs to be replaced, pull out the two fans, remove the
bolts between the first and second fans, and replace the first fan.
● When you pull out the second fan horizontally, the latch is stuck. Press the
latch and pull out the fan horizontally.
Step 7 Unscrew the fan support and take out the fan.