FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Parameter
Cold aisle
temperature
and humidity
sharing
Hot aisle
temperature
and humidity
sharing
Differential
pressure
sharing
Step 3 Perform
products in the group.
Step 4 On the home screen of the display module of any teamwork controlled smart
cooling product, tap
topology of the smart cooling product in the group is displayed.
Issue 02 (2021-04-15)
Description
This parameter can be enabled
only when at least two smart
cooling products in the group are
configured with cold aisle T/H
sensors. When this parameter is
enabled, the smart cooling
product, which is not configured
with the cold aisle T/H sensor in
the group, is logically controlled
by using the acquired value of the
configured cold aisle T/H sensor.
This parameter can be enabled
only when at least two smart
cooling products in the group are
configured with hot aisle T/H
sensors. When this parameter is
enabled, the smart cooling
product, which is not configured
with the hot aisle T/H sensor in
the group, is logically controlled
by using the acquired value of the
configured hot aisle T/H sensor.
When this parameter is enabled,
the smart cooling product, which
is not configured with the
differential pressure sensor in the
group, is logically controlled by
using the acquired value of the
configured differential pressure
sensor.
Step 1
and
Step 2
to configure teamwork control for all smart cooling
. If the teamwork control succeeds, the teamwork
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Rule
This parameter can be
enabled when at least two
smart cooling products in
the group are configured
with cold aisle T/H sensors.
This parameter can be
enabled when at least two
smart cooling products in
the group are configured
with hot aisle T/H sensors.
This parameter can be
enabled when there are at
least two smart cooling
products in the group are
configured with differential
pressure sensors.
113