FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Issue 02 (2021-04-15)
Parameter
Supply air
temp to
forcibly start
cooling
Return air
temp to
forcibly start
cooling
Cold aisle
temp to
forcibly start
cooling
DO_1 action
DO_2 action
DO_1
DO_2
Floor water
overflow
alarm action
In-cabinet
water
overflow
alarm action
Dual power
supply
setting
Power limit
function
System
power limit
Cooling
mode
control
Copyright © Huawei Technologies Co., Ltd.
C Parameter Description
Description
When the supply air temperature exceeds
the value of this parameter, the cooling
component is forcibly started.
When the return air temperature exceeds
the value of this parameter, the cooling
component is forcibly started.
When the temperature of the cold aisle
exceeds the value of this parameter, the
cooling component is forcibly started.
Set this parameter to On or Off based on
the actual scenario.
Set this parameter to On or Off based on
the actual scenario.
Set this parameter to Smoke & Water
only, Critical alarm, Major alarm,
Alarm, or Startup status based on the
actual situation.
Set this parameter to Smoke & Water
only, Critical alarm, Major alarm,
Alarm, or Startup status based on the
actual situation.
Shutdown, Inactivity, Only indoor fan
running, or Humidification stopped can
be set as required.
Set this parameter to Shutdown,
Inactivity, Only indoor fan running,
Humidifier stopped, or Comm & Humid
stopped based on site requirements.
Primary power first or Primary power
only can be set as required.
This parameter can be set to Enable or
Disable.
This parameter ensures that the total
operating power of the system is always
below the preset value.
Select a running mode.
266