8.1.7.17 How Can I Set and Add a PMAC615 AC Meter?

Prerequisites
One end of the straight-through cable has been connected to the RS485 port on
the PMAC615 AC meter, and the other end has been connected to the COM port
on the ECC800-Pro.
Context
The model of the single-phase AC meter for the lighting control box is PMAC615.
Procedure
Step 1 Set the PMAC615 communications address.
Issue 02 (2020-09-07)
Add an ATS.
Table 8-16 Adding an ATS
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
Connect To
and click Add
Device. The
parameters
Communicati
for adding
ons Port
devices are
displayed.
Device
Address
Click Test Connect to check whether the ATS connects to the ECC800-Pro
properly.
If the ATS connects to the ECC800-Pro successfully, click Confirm. The
connected devices are displayed in the Number of connected devices
list.
If the connection fails, check whether the ATS is properly connected to
the ECC800-Pro, whether the ATS and ECC800-Pro are running properly,
and whether the parameter settings are consistent with the ATS
parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select ATS from the drop-down list box.
Select ATS from the drop-down list box.
Select ECC800 from the drop-down list
box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the ATS
connects to the COM1 port on the ECC800-Pro.
If the ATS connects to another port, enter the
number of the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the ATS based on the actual
situation.