ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Figure 8-23 T/H sensor DIP switch
Step 2 Add a T/H sensor.
1.
2.
3.
Issue 02 (2020-09-07)
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Table 8-44 Adding a T/H sensor
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Manageme
nt and click
Connect To
Add Device.
The
Communicatio
parameters
ns Port
for adding
devices are
displayed.
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800-
Pro properly.
If the T/H sensor connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.
If the connection fails, check whether the T/H sensor is properly
connected to the ECC800-Pro, whether the T/H sensor and ECC800-Pro
are running properly, and whether the parameter settings are consistent
with the T/H sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H
sensor is connected to the COM3 port on the
ECC800-Pro. If the T/H sensor is connected to
another port, enter the number of the connected
port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the T/H sensor based on the
actual situation.
8 FAQ