ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 7 (Optional) If the management domain is a rack, click the management domain
and choose Design under
Otherwise, skip this step.
Step 8 In the lower-left corner of the page, click the Device tab. Click the drop-down list
box in Type and select Sensor.
Step 9 In this example, a Polymer temperature and humidity (T/H) sensor is added in the
equipment room of the root node. Select the device to be added and drag its icon
to the management domain.
Step 10 Set management attributes.
Figure 6-86 Page for setting management attributes
Step 11 Click
Step 12 Choose System > Configuration > Transmission Channel Management.
Step 13 Click Modify after selecting the IP address of the ECC800-Pro connected to the
NMS.
Issue 02 (2020-09-07)
NO TE
IP Address indicates the ECC800-Pro login IP address. Port indicates the ECC800-Pro COM2
port (3212). Device Address indicates the Polymer T/H sensor address.
to save the created device view.