High Temperature Linkage - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
4.
----End
Follow-up Procedure
After the alarm has been cleared when fire control linkage or smoke alarm
linkage occurs, perform the following operations:

6.6.1.2 High Temperature Linkage

Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 Ensure that Link high temperature with skylight open is in on state on the
Linkage Group tab page.
Issue 02 (2020-09-07)
Table 6-34 Fire sensor NO and NC definitions
Item
NO
NC
Click Submit.
Close the skylight manually.
Start the smart cooling products manually.
After turning off the lights, set Set light mode of the AC actuator to
Automatic. WebUI path: Monitoring > Aisle > AC Actuator Group > AC
Actuator > Running Parameters.
NO TE
When a smart module actuator is configured, you need to set parameters for the
smart module actuator. The setting process is similar.
The ECC800-Pro implements high temperature linkage. If it detects high
temperature alarms by interacting with multi-functional sensors and all smart
cooling products fail to communicate with the ECC800-Pro, the ECC800-Pro
opens skylights based on the alarm status to facilitate heat dissipation.
The default status of high temperature linkage is off. Set it based on the
actual situation.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Definition
Dry contact signal for the fire sensor
abnormality alarm. Closed: alarm;
open: normal
Dry contact signal for the fire sensor
abnormality alarm. Closed: normal;
open: alarm
191