ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Specifications
Table 3-46 Multi-functional sensor technical specifications
Item
Temperature
monitoring
Humidity
monitoring
Smoke
monitoring
PoE port
RS485 port
DI input
BLINK button
Test button
(smoke sensor
test button)
E-label
Indicators
Table 3-47 Description of the indicators on the multi-functional sensor
Indicator
RUN
Issue 02 (2020-09-07)
Specifications
–40°C to +70°C. Precision ≤ ±0.5°C (25°C).
0 to 100% RH. Precision ≤ ±5% RH (25°C, 20%–80% RH).
Complies with Ul217. The smoke sensor generates an alarm
when testing 3.2% weak dust for each foot.
One PoE port that complies with IEEE802.3 at
Reserves one RS485 port.
One DI input port, 12 V DC power input
Wireless communication:
● If the sensor is not connected to the network, after you hold
down the button for 2s to 3s, the sensor connects to the
network in RF_Z mode.
● If the sensor is connected to network, after you hold down
the button for 2s to 3s, the RUN indicator blinks.
● Hold down the button for more than 6 seconds to clear
network parameters.
Supports the smoke sensor test.
Hold down the button for 3s to trigger a smoke alarm, and
release the button to stop the smoke alarm.
Supported
Color
Name
Green
Module
running
status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Blinking at
The multi-functional sensor
long
successfully registers with
intervals
the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).