Fusionmodule2000 Linkage Control - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)

6.6.1 FusionModule2000 Linkage Control

Prerequisites
Linkage Grouping
Table 6-33 FusionModule2000 linkage grouping
Linkage Category
● Link smoke alarm
● Open door/turn on
Link smoke alarm with
air conditioner off
Intelligent lighting
● Link fire control
● Open door/turn on
● Link fire control
Link high temperature
with skylight open
Issue 02 (2020-09-07)
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Ensure that Enable linkage control function is Yes.
with skylight open
lights if smoke
a
alarm
a
with skylight open
lights by fire linkage
a
with air conditioner
off
Copyright © Huawei Technologies Co., Ltd.
Default Status
Function
on
If a smoke alarm is raised, the
smart module opens the skylights,
access control, and lights by
default.
off
If this linkage status is set to on
and a smoke alarm is raised, the
smart cooling products turn off
automatically.
off
If this linkage status is set to on,
an infrared alarm is raised when
the camera detects human motion,
and the aisle lights turn on
automatically for authorized door
opening.
off
If you set this linkage status to on
and a fire occurs in the smart
module, the skylights open, lights
turn on, and the access control
opens automatically, or the smart
cooling products turn off
automatically.
off
If this linkage status is set to on,
the skylights open automatically
when a high temperature alarm is
raised and all smart cooling
products fail to communicate with
the ECC800-Pro.
6 Feature Description
188