General Data, Pm240 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.2.3.1

General data, PM240

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Inrush current
Pulse frequency (factory
setting)
Electromagnetic compatibil-
ity
Braking methods
Degree of protection
Ambient operating tempera-
ture
Storage temperature
Pollution
Relative humidity
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
Installation altitude
Standards
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Version
380 V ... 480 V 3-ph. AC ± 10 %
0 V 3-ph. AC ... input voltage x 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 550 Hz, depending on the control mode
0.7 ... 0.85
< LO base load input current
4 kHz for 0.37 kW ... 90 kW
2 kHz for 110 kW ... 250 kW
The devices are suitable for environments, Categories C1 and C2 according to IEC/EN
61800-3: 2004.
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20 chassis units
0 °C ... +40 °C
LO base load power
HO base load power
0 °C ... +50 °C
HO base load power
Up to 60° C
with derating, see also Restrictions for special ambient conditions
(Page 428)
-40 °C ... +70 °C
Protected according to pollution degree 2 to EN 61800-5-1: 2007
< 95% - condensation not permissible
EN 60721-3-3; 1995
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
up to 1000 m above sea level
up to 2000 m above sea level
up to 4000 m above sea level
UL, cUL, CE, C-tick, SEMI F47
The drive only satisfies the UL requirements when UL-certified fuses are used.
10.2 Technical data, Power Modules
Can be set in 2 kHz steps in the range from 2 kHz
... 16 kHz. If you increase the pulse frequency, the inverter
reduces the maximum output current.
0.37 kW ... 250 kW
132 kW ... 200 kW
0.37 kW ... 110 kW
0.37 kW ... 132 kW
160 kW ... 250 kW
with derating, see also Restrictions for special ambient con-
ditions (Page 428)
Technical data
407