Alarms, faults and system messages

9.1 Operating states indicated on LEDs

9.1
Operating states indicated on LEDs
The LED RDY (Ready) is temporarily orange after the power supply voltage is switched-on.
As soon as the color of the LED RDY changes to either red or green, the LEDs signal the
inverter state.
Signal states of the LED
In addition to the signal states "on" and "off" there are two different flashing frequencies:
Table 9- 1
Table 9- 2
348
Inverter diagnostics
LED
RDY
GREEN - on
Not relevant
GREEN - slow
RED - on
YELLOW - variable
RED - slow
RED - fast
Not relevant
RED - fast
Communication diagnostics via PROFINET
LNK LED
Explanation
GREEN - on
The communication via PROFINET is in order.
GREEN - slow
Device naming is active.
Off
No communication via PROFINET.
Explanation
BF
There is presently no fault
Commissioning or reset to factory settings
Firmware update in progress
frequency
RED - slow
Inverter waits until the power supply is switched off
and switched on again after a firmware update
There is presently a fault
RED - fast
Incorrect memory card or unsuccessful firmware
update
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB