Siemens SINAMICS G120 Operating Instructions Manual page 272

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.7 Application-specific functions
Parameter using the free technology controller 0 as example
Parameter
p11000
p11053
p11057,
p11058
p11063
p11064
p11065
p11067
p11068
p11071
p11074
p11080
p11085
p11091
p11092
r11094
You can find the complete parameter list in the List Manual.
272
Remark
BI: Free tec_ctrl 0 enable (Factory setting: 0)
1 signal:
Technology controller is enabled.
CI: Free tec_ctrl 0 setpoint signal source (Factory setting: 0)
Free tec_ctrl 0 setpoint ramp-up time and ramp-down time (Factory setting: 1 s)
Free tec_ctrl 0 error signal inversion (Factory setting: 0 s)
0:
No inversion
1:
Inversion
p11063 must be set = 1 if the actual value decreases with increasing motor
speed.
CI: Free tec_ctrl 0 actual value signal source (Factory setting: 0)
Free tec_ctrl 0 actual value smoothing time constant (Factory setting: 0 s)
Free tec_ctrl 0 actual value upper limit (Factory setting: 100 %)
Free tec_ctrl 0 actual value lower limit (Factory setting: -100 %)
Free tec_ctrl 0 actual value inversion (Factory setting: 0)
0:
No inversion
1:
Inversion
Free tec_ctrl 0 differentiation time constant (T
Free tec_ctrl 0 proportional gain (K
Free tec_ctrl 0 integral time (T
CO: Free tec_ctrl 0 maximum limit (Factory setting: 100 %)
CO: Free tec_ctrl 0 minimum limit (Factory setting: 0 %)
CO: Free tec_ctrl 0 output signal
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
) (Factory setting: 0 s)
d
) (Factory setting: 1.0)
P
) (Factory setting: 30 s)
I
Converter with CU230P-2 Control Units