Technical Data, Pm230; General Data, Pm230 - Ip20 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.2.1

Technical data, PM230

Typical inverter load cycles
Figure 10-2
10.2.1.1

General data, PM230 - IP20

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance
Inrush current
Pulse frequency (factory set-
ting)
Electromagnetic compatibility
Braking methods
Degree of protection
Operating temperature at
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Duty cycles, "High Overload" and "Low Overload"
Version
380 V ... 480 V 3-ph. AC ± 10 %
0 V 3-ph. AC ... input voltage x 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 550 Hz, depending on the control mode
0.9
Uk ≤ 1%, no line reactor permitted
< LO base load input current
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 55 kW
and 75 kW). An increase in the pulse frequency results in a lower output current.
Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2
environments.
DC braking
IP20 built-in units
IP20 when mounted in a control cabinet
PT devices
IP54 on the control cabinet wall
LO base load power without derating
Technical data
10.2 Technical data, Power Modules
0 °C ... +40 °C
373