Technical data
10.2 Technical data, Power Modules
10.2.6
PM330 technical data
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 10-7
10.2.6.1
PM330 general data
Table 10- 61 General technical data
Electrical data
Line system configurations
Line requirement
Line voltage
Line frequency
Output frequency
Displacement factor cos φ
power factor λ
Inverter efficiency
Short-circuit current rating
per IEC, in conjunction with
the specified fuses
Short-circuit current rating
per UL508C (up to
480 VAC), in conjunction
with the specified fuses
Overvoltage category
Mechanical data
Degree of protection
Protection class
Cooling method
Sound pressure level L
PA
ma)
Touch protection
422
Load cycles, Low Overload" and "High Overload"
Grounded TN/TT systems and non-grounded IT systems
A line reactor (2 % u
380 V (-10 %) ... 480 V (+10 %)
47 ... 63 Hz
0 ... 100 Hz
0.96
0.75 ... 0.93 (with line reactor u
> 98 %
160 ... 400 kW: 100 kA
160 ... 400 kW: 100 kA
Can be used on supply systems that cannot supply more than 100 kA symmetrically for a
maximum voltage of 480 VAC when they are protected with the listed fuses of type Class J
or Class L, or approved semi-conductor fuses specified in the "Technical Data" section of
this manual.
III according to EN 61800-5-1
IP20
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Forced air cooling AF according to EN 60146
(1
≤ 74 dB(A)
1)
according to EN 61800-5-1: For the intended purpose
) must be connected in series
k
= 2 %)
k
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Converter with CU230P-2 Control Units