Advanced commissioning
6.7 Application-specific functions
Table 6- 43
Order of deactivation for external motors depending on setting in p2371
p2371
Activated motors
1
M1
2
M1+M2
3
M1+M2
4
M1+M2+M3
5
M1+M2+M3
6
M1+M2+M3
7
M1+M2+M3
8
M1+M2+M3
If you are using motors of the same power rating, you can use p2372 to define whether the
motors are to be activated/deactivated following the setting specified in p2371 (p2372 = 0) or
based on the operating hours (p2372 = 1, 2 ,3. Details see parameter list).
Parameters to set and activate the cascade control:
p0730 = r2379.0
p0731 = r2379.1
p0732 = r2379.2
p2200 = 1
p2251 = 0
p2370
p2371
p2372
p2373
p2374
p2375
p2376
p2377
p2378
r2379
298
Stage 1
Stage 2
M1
M1+M2
M1
M1+M2
M2
M1+M2+M3
M1+M2
M1+M2+M3
M3+M1
M1+M2+M3
M3+M2
M1+M2+M3
M3+M1
M1+M2+M3
M3+M2
Signal source for digital output 0
Control external motor 1 via DO 0
Signal source for digital output 1
Control external motor 2 via DO 1
Signal source for digital output 2
Control external motor 3 via DO 2
Technology controller release
Activate technology controller
Technology controller mode
Technology controller as main speed setpoint
Cascade control - enable
signal source for cascade control on/off
Cascade control - activate the configuration for the cascade control and define
the switch-in sequence
Cascade control - motor selection mode
Define automatic motor switch-on
Cascade control - switch-in threshold
Define switch-on threshold
Cascade control - switch-in delay
Define delay time
Cascade control - deactivation delay
Define the delay time for deactivating the cascade control
Cascade control - overcontrol threshold
Define overcontrol threshold
Cascade control - interlock time
Define interlock time
Cascade control - connect/disconnect speed
Defining the speed for the main drive after connecting/disconnecting a motor
Cascade control - status word
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Stage 3
Stage 4
M1
M1
M3
M1
M2+M1
M2
M3
M2+M1
M3+M1
M3
Converter with CU230P-2 Control Units
Stage 5
Stage 6
M1
M1
M2
M1