Technical Data; Technical Data For Cu230P-2 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data

10.1

Technical data for CU230P-2

Feature
Article Nos.
Operating voltage
Current consumption
Power loss
Output voltages
Setpoint resolution
Digital inputs
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Data / explanation
CU230P-2 CAN
CU230P-2 HVAC
CU230P-2 BT
CU230P-2 DP
CU230P-2 PN
You have two options for the Control Unit power supply:
Supply from the Power Module
External supply via terminals 31 and 32 with 20.4 V ... 28.8 V DC.
Use a power supply with protective extra low voltage (PELV according to EN 61800-5-1),
Class 2.
The 0 V of the power supply must be connected to the PE of the plant/system through a
low-ohmic connection.
Max 0.5 A
The current consumption can be higher if the Control Unit supplies external components.
5.0 W
+24 V out (terminal 9), 18 V ... 28.8 V, max. 100 mA
+10 V out (terminals 1 and 35), 9.5 V ... 10.5 V, max. 10 mA
0.01 Hz
6 (DI 0 ... DI 5)
With CANopen interface
With RS485 interface for the following
protocols:
USS
Modbus RTU
BACnet MS/TP
P1
With PROFIBUS interface
With PROFINET interface
Low < 5V, high > 11V
Electrically isolated
30 V maximum input voltage
5.5 mA current consumption
SIMATIC-compatible
PNP/NPN switchable
10 ms response time for debounce time p0724 = 0.
10
Article numbers: See
Section Control Units
(Page 27)
369