Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
9.
10.
11.
12.
13.
14.
15.
16.
17.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
130
Select the application:
VEC STD
PUMP FAN Speed-dependent load: Typical applications include
Select the default setting for the interfaces of the inverter that is suita-
ble for your application. You will find the available default settings in
Section: Default setting of the interfaces (Page 88)
Minimum/maximum frequency of the motor
Scaling of analog input 0
Motor ramp-up time.
Motor ramp-down time
Ramp-down time for the OFF3 command
Complete the basic commissioning:
17.1. Switchover the display using an arrow key: nO → YES
17.2. Press the OK key.
Constant load: Typical applications include belt conveyor
drives.
pumps and fans.
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Converter with CU230P-2 Control Units