Technical Data, Pm240-2; General Data, Pm240-2 - 200 V - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.2 Technical data, Power Modules
10.2.2

Technical data, PM240-2

Typical inverter load cycles
Figure 10-3
10.2.2.1

General data, PM240-2 - 200 V

Property
Line voltage
Output voltage
Input frequency
Output frequency
Line impedance
Power factor λ
Inrush current
Overvoltage category acc.
to EN 60664-1
Pulse frequency
Short-circuit current rating
(SCCR)
Electromagnetic compati-
bility
Braking methods
388
"Low Overload" and "High Overload" load cycles
Version
FSA ... FSC
200 V ... 240 V 1-ph. AC ± 10 % for LO base load power 0.55 kW ... 4 kW
200 V ... 240 V 3-ph. AC
± 10 %
FSD ... FSE
200 V ... 240 V 3-ph. AC -20 % / + 10 %
3 AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
FSA ... FSC: Uk ≥ 2 %, for lower values, we recommend a line reactor, or a Power Module
with the next higher power rating.
Not applicable for FSD and FSE
FSA ... FSC
0.7 without line reactor for Uk ≥ 2 %
0.85 with line reactor for Uk < 2%
FSD ... FSE
0.95 line reactor is not required
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
4 kHz (factory setting),
Can be set in 2 kHz steps in the range from 2 kHz ... 16 kHz. If you increase the pulse fre-
quency, the inverter reduces the maximum output current.
≤ 65 kA rms
Devices with integrated filter are suitable for Category C2 environments according to IEC/EN
61800-3.
DC braking, compound braking, dynamic braking with integrated braking chopper
for HO base load power 0.37 kW ... 3 kW
for LO base load power 0.55 kW ... 7.5 kW
for HO base load power 0.37 kW ... 5.5 kW
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p