Figure 6-50
Controlling the activation and deactivation of motors
Use p2371 to determine the order of activation/deactivation for the individual external
motors.
Table 6- 42
Order of activation for external motors depending on setting in p2371
p2371
Significance
0
Cascade control deactivated
1
One motor can be activated
2
Two motors can be activated
3
Two motors can be activated
4
Three motors can be activated
5
Three motors can be activated
6
Three motors can be activated
7
Three motors can be activated
8
Three motors can be activated
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Conditions for activating/deactivating an uncontrolled motor
Stage 1
Stage 2
---
M1
M1
M1+M2
M1
M2
M1
M1+M2
M1
M3
M1
M2
M1
M1+M2
M1
M2
6.7 Application-specific functions
Stage 3
Stage 4
M1+M2
M1+M2+M3
M1+M3
M1+M2+M3
M1+M2
M2+M3
M3
M1+M3
M3
M1+M3
Advanced commissioning
Stage 5
Stage 6
M1+M2+M3
M1+M2+M3
M2+M3
M1+M2+M3
297