Power-Dependent Data, Pm260 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.2.5.2

Power-dependent data, PM260

Note
The values for Low Overload (LO) are identical with those of the rated values.
Table 10- 59 PM260, IP20, frame sizes D - 3 AC 660 V ... 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse
Power losses without filter
Power losses with filter
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
Sound pressure level
Table 10- 60 PM260, IP20, frame sizes F - 3 AC 660 V ... 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse
Power losses without filter
Power losses with filter
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
Sound pressure level
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
6SL3225-...
0BH27-5UA1
6SL3225-...
0BH27-5AA1
11 kW
13 A
14 A
7.5 kW
10 A
10 A
20 A
22 l/s
2.5 ... 16 mm
14 ... 6 AWG
1.5 Nm / 53 lbf in
22 kg
23 kg
< 64 dB(A)
6SL3225-...
0BH32-2UA1
6SL3225-...
0BH32-2AA1
30 kW
34 A
35 A
22 kW
26 A
26 A
50 A
94 l/s
10 ... 35 mm
8 ... 2 AWG
6 Nm / 53 lbf in
56 kg
58 kg
< 70 dB(A)
10.2 Technical data, Power Modules
0BH31-1UA1
0BH31-1AA1
15 kW
18 A
19 A
11 kW
13 A
14 A
20 A
22 l/s
4 ... 16 mm
2
2
12 ... 6 AWG
1.5 Nm / 53 lbf in
22 kg
23 kg
< 64 dB(A)
0BH33-0UA1
0BH33-0AA1
37 kW
41 A
42 A
30 kW
34 A
35 A
50 A
94 l/s
16 ... 35 mm
2
2
6 ... 2 AWG
6 Nm / 53 lbf in
56 kg
58 kg
< 70 dB(A)
Technical data
0BH31-5UA1
0BH31-5AA1
18.5 kW
22 A
23 A
15 kW
18 A
19 A
32 A
39 l/s
6 ... 16 mm
2
10 ... 6 AWG
1.5 Nm / 53 lbf in
22 kg
23 kg
< 64 dB(A)
0BH33-7UA1
0BH33-7AA1
55 kW
60 A
62 A
37 kW
41 A
42 A
80 A
117 l/s
25 ... 35 mm
2
4 ... 2 AWG
6 Nm / 53 lbf in
56 kg
58 kg
< 70 dB(A)
421

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents