10.3 Restrictions for special ambient conditions

10.3
Restrictions for special ambient conditions
Current de-rating depending on the ambient operating temperature
The Control Unit and operator panel can restrict the maximum permissible operating ambient
temperature of the Power Module.
Current derating depending on the installation altitude
Above 1000 m above sea level you must reduce the inverter output current as a result of the
lower cooling capability of the air.
428
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB