Procedure with Startdrive
To safely remove the memory card, proceed as follows:
1. In the Drive Navigatorselect the following screen form:
2. Click on the button to safely remove the memory card.
Startdrive will tell you whether you can remove the memory card from the inverter.
You have now safely removed the memory card from the inverter.
Safely removing a memory card using the BOP-2
Procedure
To safely remove the memory card using BOP-2, proceed as follows:
1.
2.
3.
4.
You have now safely removed the memory card using BOP-2.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Go to parameter p9400. If a memory card is correctly inserted, then
p9400=1.
Set p9400 = 2.
The inverter sets p9400 = 3 or p9400 = 100.
• p9400 = 3: You may remove the memory card from the inverter.
• p9400 = 100: It is not permissible that you remove the memory
card. Wait for several seconds and then set p9400 = 2 again.
Remove the memory card. After removing the memory card,
p9400 = 0.
Backing up data and series commissioning
7.1 Backing up and transferring settings using a memory card