Current reduction depending on pulse frequency
Table 10- 22 Current reduction depending on the pulse frequency
LO base
load
0.37
0.55
0.75
11.0
15.0
18.5
The permissible motor cable length also depends on the cable type and the selected pulse fre-
1)
quency.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Output base-load current at a pulse frequency of
2 kHz
4 kHz
kW
A
A
--
1.30
--
1.70
--
2.20
1.1
--
3.10
1.5
--
4.10
2.2
--
5.90
3.0
--
7.70
4.0
--
10.20
5.5
--
13.20
7.5
--
18.00
--
26.00
--
32.00
--
38.00
22
--
45.00
30
--
60.00
37
--
75.00
45
--
90.00
55
--
110.0
75
--
145.0
10.2 Technical data, Power Modules
6 kHz
8 kHz
10 kHz
A
A
A
1.11
0.91
0.78
1.45
1.19
1.02
1.87
1.54
1.32
2.64
2.17
1.86
3.49
2.87
2.46
5.02
4.13
3.54
6.55
5.39
4.62
8.67
7.14
6.12
11.22
9.24
7.92
15.30
12.60
10.80
22.10
18.20
15.60
27.20
22.40
19.20
32.30
26.60
22.80
38.25
31.50
27.00
51.00
42.00
36.00
63.75
52.50
45.00
76.50
63.00
54.00
93.50
77.00
66.00
123.3
101.5
--
Technical data
1)
12 kHz
14 kHz
A
A
0.65
0.59
0.85
0.77
1.10
0.99
1.55
1.40
2.05
1.85
2.95
2.66
3.85
3.47
5.10
4.59
6.60
5.94
9.00
8.10
13.00
11.70
16.00
14.40
19.00
17.10
22.50
20.25
30.00
27.00
37.50
33.75
45.00
40.50
55.00
49.50
--
--
16 kHz
A
0.52
0.68
0.88
1.24
1.64
2.36
3.08
4.08
5.28
7.20
10.40
12.80
15.20
18.00
24.00
30.00
36.00
44.00
--
387