Siemens SINAMICS G120 Operating Instructions Manual page 132

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
9.
10.
10.
11.
12.
13.
14.
15.
16.
17.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
132
Select the application:
OP LOOP Recommended setting for standard applications.
CL LOOP
HVY LOAD Recommended setting for applications with a high break
The BOP-2 does not display this step for a PM330 Power Module.
Select the default setting for the interfaces of the inverter that is suita-
ble for your application. You will find the available default settings in
Section: Default setting of the interfaces (Page 88)
Minimum and maximum frequency of the motor
Scaling of analog input 0
Motor ramp-up time.
Motor ramp-down time
Ramp-down time for the OFF3 command
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
ST RT OP Recommended setting: Measure the motor data at stand-
STILL OP
Complete the basic commissioning:
17.1. Switchover the display using an arrow key: nO → YES
17.2. Press the OK key.
Recommended setting for applications with short ramp-
up and ramp-down times. This setting is not suitable for
hoisting gear and cranes/lifting gear.
loose torque.
No measurement of motor data.
still and with the motor rotating.
Measure the motor data at standstill.
Select this setting if the motor cannot freely rotate, e.g.
for a mechanically limited traversing range.
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB