3.12 Battery Connection; Figure 3-13: Outlet Voltage Measurement Points; Figure 3-14: Battery Connections - Honeywell ADEMCO MX8000 Installation And Operation Manual

Digital alarm receiver
Hide thumbs Also See for ADEMCO MX8000:
Table of Contents

Advertisement

3.12 Battery Connection

To install the backup battery, follow these steps:
Note: A UL approved 12VDC 7AH battery (such as a Powersonic 1270) will provide a minimum of 4 hours of
battery backup power. (See 2.4.2 for UL requirements.)
1. Plug the Battery/Relay wiring harness onto the connector on the back of the MX8000 receiver. (See
Figure 3–14.)
2. Connect the RED terminal to the positive (+) side of the battery.
3. Connect the BLACK terminal to the negative (-) side of the battery.
Note: Incorrect polarity can damage the battery and the MX8000.
Larger
Slotted
Hole
Ground
Hole
Figure 3–13: Outlet Voltage Measurement Points
Red: Battery Positive
Figure 3–14: Battery Connections
C
Smaller
Slotted
Hole
B
A
120 VAC ± 10%
240 VAC ± 10%
50-60 Hz
100 VA
WARNING!
HIGH VOLTAGE PRESENT
DISCONNECT AC LINE AND
ALL OTHER CONNECTORS
PROIR TO SERVICING
RELAY RATING
2.5A 48VAC/VDC
COM 1
BATT-
BATT+
RLY NC
PARALLEL
COM 2
Black: Battery Negative
Replace Battery
Every 5 Years
Section 3 – Installation
FUSE
2.5A
SLOW BLOW
REPLACE ONLY
WITH A FUSE
OF SAME TYPE
UNUSED
RLY NO
RLY COM
3–11