3.10.1 Printer Cable Pin-Outs; Table 3-1: External Printer Cable Pin Description; Figure 3-8: Parallel Printer Cable Connection To Mx8000; Figure 3-9: Wiring Sequence For Parallel Printer Port Interface - Honeywell ADEMCO MX8000 Installation And Operation Manual

Digital alarm receiver
Hide thumbs Also See for ADEMCO MX8000:
Table of Contents

Advertisement

MX8000 Installation and Operation Guide
3. Turn the printer power "on".

3.10.1 Printer Cable Pin-Outs

25 pin printer cables are standard items at most electronic stores; however, if you create your own cable, use
the pin description in Table 3–1.
MX8000 Pin #
Signal
1
Data Strobe (Low)
2
Data Bit 1
3
Data Bit 2
4
Data Bit 3
5
Data Bit 4
6
Data Bit 5
7
Data Bit 6
8
Data Bit 7
9
Data Bit 8
10
/AckNlg
11
Busy
12
Paper Empty
13
Select
14
Not used
15
Not used
16
Logic ground
17
Not used
18 to 25
Logic Ground
Figure 3–9 shows the wiring sequence of this connector.
Figure 3–9: Wiring Sequence For Parallel Printer Port Interface
3–8
NOTE: FOR UL APPLICATIONS, A
STANDBY PRINTER MUST
BE AVAILABLE TO BE PUT
INTO OPERATION WITHIN
30 SECONDS. ONE STANDBY
PRINTER MUST BE AVAILABLE
FOR EVERY 5 PRINTERS.
Figure 3–8: Parallel Printer Cable Connection to MX8000
Table 3–1: External Printer Cable Pin Description
Direction
Out
Out
Out
Out
Out
Out
Out
Out
Out
In
In
In
In
-
-
-
-
-
Receiver
Pin 1
Pin 14
120 VAC ± 10%
240 VAC ± 10%
50-60 Hz
100 VA
WARNING!
HIGH VOLTAGE PRESENT
DISCONNECT AC LINE AND
ALL OTHER CONNECTORS
PROIR TO SERVICING
RELAY RATING
2.5A 48VAC/VDC
COM 1
BATT-
BATT+
RLY NC
PARALLEL
COM 2
TO PRINTER
Description
A low strobe pulse to read data into the printer. The
pulse width is greater than 0.5 microseconds.
These signals represent information of the first to
eighth bits of parallel data. Each signal is at high
level when the data is logic 1 and low when it is
logic 0.
A low pulse from the printer signals the control that
the printer is ready for additional data.
A high level indicates that the printer is busy.
A high level indicates that the printer is out of paper.
A low level indicates the printer is offline or in an
error condition.
-
-
Logic ground for printer
-
Ground return for data lines.
10.0'
Pin 13
NOTE: 10' is the
MX8000
Pin 25
FUSE
2.5A
SLOW BLOW
REPLACE ONLY
WITH A FUSE
OF SAME TYPE
UNUSED
RLY NO
RLY COM
Printer
maximum
recommended
cable length.

Advertisement

Table of Contents
loading

Table of Contents