• Event on delay
The number of the event to be delayed and the delay time can be set regardless of
event type. The delay turns on the output for the duration of the delay when the event
meets the conditions for going from OFF to ON. When this function is combined
with the event standby function, the event on delay operates when the standby state is
cleared.
• Segment event progress
• The output stays OFF until the program reaches a segment with an event.
• The event goes ON or OFF according to the set value of the event.
• Previous settings are valid until segments with other event settings are reached.
• Previous settings are valid when the program has reached segment number 1 using
the cycle function or pattern link function. The output is turned off if there is no
event in segment number 1.
• Other functions
The MV forward/backward event does not operate when the
set to 0 during SP output (programmer function).
Normal PV2 upper and lower limit operation events and PV1-PV2 differential of
upper limit and lower limit events during automatic PV channel switching do not
operate on models with only one PV input channel.
Normal PV1 upper and lower limit operation event and normal PV2 upper and lower
limit operation events operate in the READY mode.
PV upper limit
Normal PV1 upper limit operation
Normal PV2 upper limit operation
H
EV
Deviation upper limit
Deviation upper limit with standby
H
SP+EV
Absolute value deviation upper limit
Absolute value deviation upper limit with standby
SOAK absolute value deviation upper limit
SOAK absolute value deviation upper limit with standby
H
EV
SP
Items marked
operate only in SOAK segments.
*
PV lower limit
Normal PV1 lower limit operation
Normal PV2 lower limit operation
PV
Deviation lower limit
Deviation lower limit with standby
PV
Absolute value deviation lower limit
Absolute value deviation lower limit with standby
SOAK absolute value deviation lower limit
*
SOAK absolute value deviation lower limit with standby
*
H
PV
EV
Items marked
Chapter 5. FUNCTIONS
C21
setup data setting is
H
EV
H
SP+EV
*
H
H
EV
EV
SP
operate only in SOAK segments.
*
PV
PV
*
PV
5-9