Honeywell DCP551 Mark ΙΙ User Manual page 179

Digital control programmer
Table of Contents

Advertisement

PID group, output limiter group number items cannot be displayed with ↑ and ↓ keys
Cause
Programmer function on
Programming item display off
G.SOAK items, PV shift items and repeat items cannot be displayed with ↑ and ↓ keys
Cause
Programming item display off
PV start items, cycle items and pattern link items cannot be displayed with ↑ and ↓ keys
Cause
Programming item display off
Segment insertion and deletion cannot be confirmed with FUNC and ENTER keys
Cause
Set to memory protect.
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Not set to pattern item on programming map. Move to the pattern item on the programming map.
This segment is not set on the programming
map.
Program deletion cannot be confirmed with FUNC and ENTER keys during pattern item registration
Cause
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Chapter 10. TROUBLESHOOTING
Set setup data
to something other than 0.
C21
Set setup data
to 0.
C58
Set setup data
to 0.
C59
Set setup data
to 0.
C60
Set variable parameter
PA02
Set READY mode to execute RESET operation (
RUN/HOLD keys
).
Move to a set segment or set the segment.
Set READY mode to execute RESET operation (
RUN/HOLD keys
).
Measure
Measure
Measure
Measure
to 0, 2 or 4.
PROG +
Measure
PROG +
10-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcp550

Table of Contents