Chapter 7. PARAMETER SETUP
No.
Item code
External switch input RSW5
71
C 71
External switch input RSW6
72
C 72
External switch input RSW7
73
C 73
External switch input RSW8
74
C 74
External switch input RSW9
75
C 75
to 16 (program selection)
Communication address
76
C 76
Transmission rate
77
C 77
Transmission code
78
C 78
Communication
79
C 79
Communication method
80
C 80
ROM ID
81
C 81
82
ROM ITEM
C 82
ROM revision
83
C 83
Data version
84
C 84
CPU board ID
85
C 85
I/O board ID
86
C 86
Unused
87
C 87
Unused
88
C 88
Unused
89
C 89
PID type
90
C 90
PV1 burnout
91
C 91
PV2 burn out
92
C 92
Time proportional output system
93
C 93
Unused
94
C 94
7-26
Factory default
Item
settings
0
0
0
0
0
0
0
0
0
0
Ð
Ð
Ð
Ð
Ð
Ð
----
----
----
1
0
0
0
----
User
Settings and descriptions
settings
0 : NOP (does not function)
1 : RAMP-E
2 : FAST
3 : G.SOAK is cleared using OR
4 : G.SOAK is cleared using AND
5 : MANUAL/AUTO
6 : AT start/terminate
7 : PV1/PV2
8 : Auto load
®
9 : PV1
PV2 wait
®
10: PV2
PV1 wait
11: NOP (does not function)
12: Normal operation/reverse operation
0: BCD4 bit x 2 digits
1: binary 7 bits
0 to 127
[Description:]
----- is displayed and setting cannot be performed on
model without communications.
When
is set to 0, the communication function is not
C76
activated.
0: 9600bps
1: 4800bps
2: 2400bps
3: 1200bps
[Description:]
----- is displayed and setting cannot be performed on
model without communications.
0: 8 bits, even parity, 1 stop bit
1: 8 bits, no parity, 2 stop bits
[Description:]
----- is displayed and setting cannot be performed on model without
communications.
0: CPL
1: ST221 (no PV trend)
2: ST221 (PV trend)
[Description:]
----- is displayed and setting cannot be performed on model without
communications.
0 : RS-485
1 : RS-232C
[Description:]
----- is displayed and setting cannot be performed on model without
communications.
[Description:]
Can only be referenced for mechanical service use.
[Description:]
----- is displayed and setting cannot be performed.
0: Improved
1: Compatible with Mark
0: Yes
1: No
0: Yes
1: No
[Description:]
----- is displayed and setting cannot be performed on
model with one PV input channel.
0: Does not go on a second time off in time proportional cycle.
1: Goes on a second time in time proportional cycle.
[Description:]
----- is displayed and setting cannot be performed.
1