4-9 Event Output (Open Collector Output) Connection
EV1 EV2 EV3 EV4 EV5 EV6 EV7 EV8
5
6
7
EV9 EV10 EV11 EV12 EV13 EV14 EV15 EV16
11 22 23 27 28 31 32 24
10
HANDLING PRECAUTIONS
8 17 18 19 20 9
• Do not short-circuit the positive (+) terminal of the external power supply to
terminals (5) to (8), (17) to (20), (10), (11), (22), (23), (27), (28), (31), and (32)
on the DCP551. Doing so causes the open collector outputs to malfunction.
(There is no short circuit preventing circuit inside.)
• When connecting a semiconductor load such as a programmable controller
(sequencer), select a module in which the current directions match.
Use one made inoperative by the leakage current produced when the digital
outputs are shut off.
+
External power supply
12 to 24Vdc
-
Max. load current
Max. common current
Leakage current when OFF
+
External power supply
12 to 24Vdc
-
Max. load current
Max. common current
Leakage current when OFF
Chapter 4. WIRING
: 70mA/point
: 500mA
: less than 0.1mA
: 70mA/point
: 500mA
: less than 0.1mA
4-11