Chapter 11. SPECIFICATIONS
Item
General
Action when power supply turns on
specifications
Service interruption dead time
Insulation resistance
Withstand voltage
Standard conditions
Operating conditions
Transportation and
storage conditions
Terminal screw
Terminal screw tighten torque
Mask and case material
Mask and case color
Mounting
Mass
11-6
Reset time: 10ms max. (time until normal operation possible under normal
operating conditions)
Lower than 20ms (under the action conditions)
Higher than 50M
under 500Vdc megger between power supply terminal
(39)or(40) and FG terminal ((52)or(53))
1500V AC 50/60Hz for 1min between power terminal and frame ground terminal
Note: Primary and secondary sides are capacitive coupled inside the DCP551.
Thus disconnect the ground wire from the secondary side terminal (for
example, when using a grounded thermocouple) before performing a
withstand voltage test. Failure to do so may result in equipment damage.
Ambient temperature
23
Ambient humidity
60
Rated power supply voltage 105V ac 1%
Power supply frequency 50
Vibration resistance
0m/s
Shock resistance
0m/s
Mounting angle
Reference plane (vertical) 3
Ambient temperature
0 to 50 C (the ambient temperature at the bottom of the
range
case when hermetically sealed inside case)
Ambient humidity range
0 to 90% RH (non-condensing)
Rated power supply voltage 105V ac
Allowable power supply voltage 90 to 264V ac
Power supply frequency 50
Vibration resistance
0 to 1.96m/s
Shock resistance
0 to 9.80m/s
Mounting angle
Reference plane (vertical) 10
Altitude
2000m max.
Ambient temperature
-20 to 70 C
range
Ambient humidity range
10 to +95% RH (non-condensing)
Vibration resistance
0 to 4.90m/s
2hours each)
Shock resistance
0 to 490m/s
Package drop test
Drop height 60cm (Free drop at 1 corner, 3 edges, 6 faces)
M3.5 self-up screw
0.78 to 0.98N . m
Mask : Multiron
Case : Multiron
Musk : Dark gray (Munsell sign 5Y3.5/1)
Case : Light gray
Panel flush-mount
About 1.5kg
Specifications
2 C
5% RH
1Hz or 60 1Hz
2
2
2Hz or 60
2Hz
2
2
2
(10 to 60Hz in X, Y and Z directions,
2
(in vertical direction, 3 times)

Hide quick links: